Sine-wave filters: they convert the pulses from the frequency converter into a sinusoidal voltage, greatly reduce the stress on the motor insulation and the motor noise, and lower the motor losses. With this filter, the motor cable can be up to 300 m long (Grundfos catalogue and manual).
When is a filter required? According to the CUE manual: sine-wave filter with SP, BM and BMB pumps with motors of 380 V and above, with MG71 and MG80 motors up to 1.5 kW connected to a CUE above 1.5 kW, with motors of 500 V and above, and for a high reduction of voltage peaks and noise; dU/dt filter for a lower reduction, cable up to 150 m. SPE pumps require a sine-wave filter compatible with permanent-magnet motors.
MCB 114 module: it adds to the CUE an analogue input 0 / 4-20 mA for an additional sensor and two Pt100 / Pt1000 inputs for temperature sensors, used to monitor the temperature of submersible motors controlled by a frequency converter.
Mounting options: the control panel can be remote-mounted on a cabinet door with the GLCP option (panel not included; it comes from the CUE or is bought as a spare part); a floor-mounting option is also available.
Applications: CUE installations with SP and SPE submersible pumps, long motor cables, motor temperature monitoring, cabinet integration.
Dry-running protection: digital inputs 2 to 4 of the CUE accept a Grundfos LiqTec sensor, a pressure sensor or a float switch on the suction side: the pump stops and does not restart as long as the input is activated (CUE manual).
Official Grundfos distributor, SINES Export supplies CUE frequency converters, their filters and their accessories to installers, integrators, engineering firms and operators, for worldwide export. Send us the motor nameplate and the cable length: we select the right CUE size and filter. See also the SP submersible pumps, the variable-speed SPE pumps and the CR and CRN pumps.
When is an output filter required?
| Use case (CUE manual) |
CUE power |
dU/dt filter |
Sine-wave filter |
| SP, BM, BMB pumps with motors of 380 V and above | all | – | 0 to 300 m |
| MG71 and MG80 motors up to and including 1.5 kW | CUE above 1.5 kW | – | 0 to 300 m |
| Reduction of dU/dt and noise, low reduction | all | 0 to 150 m | – |
| Reduction of dU/dt, voltage peaks and noise, high reduction | all | – | 0 to 300 m |
| Motors of 500 V and above | all | – | 0 to 300 m |
With a sine-wave filter, the motor cable can be up to 300 m long; with a dU/dt filter, 150 m. The cable between the CUE and the filter must be kept short (Grundfos manual).
Common CUE specifications
| Specification |
Value |
| Function | external frequency converter designed for Grundfos pumps, with a start-up guide for each pump family (CR, CRI, CRN, CRT, SP, SP-G, SP-NE…) |
| Control modes | open loop, constant pressure, constant or proportional differential pressure, constant flow rate, constant temperature, constant level, other constant value |
| Inputs and outputs | 1 RS-485 GENIbus port, 1 analogue input 0-10 V / 0-4-20 mA for the external setpoint, 1 analogue input 0-4-20 mA for the sensor, 1 analogue output 0-20 mA, 4 digital inputs (start / stop and 3 programmable), 2 programmable relays |
| Communication | GENIbus as standard; other protocols via a CIU communication unit |
| Motor cable | screened to comply with EN 61800-3; 150 m maximum screened, 300 m unscreened; beyond that, please consult us |
| Installation | IP20 / IP21 in a cabinet only; IP54 / IP55 never outdoors without protection against water and sun |
| Altitude | above 2 000 m, the CUE derates its output: a larger size may be required |
Sources: Grundfos CUE manual, Grundfos SPE data booklet and Grundfos 2026 catalogue.
Official Grundfos documents.
The online manual covers CUE units from 0.55 to 90 kW; for sizes of 110 kW and above, we supply the corresponding Grundfos manual with the quotation.
To select the size and the filter, contact us with the motor nameplate, the site voltage and the motor cable length.