The motor cable is chosen according to the motor, and its length according to the depth of the joint: MS 402 in 4G1.5 with plug (1.7 to 30 m), MS 4000 in 4G1.5 or 4G2.5 with plug, RE version for aggressive water (2 to 60 m), MS 6000 in 4G6 or 4G10 (5 to 30 m). The joint is generally made above the pump; the submersible cable, with a calculated cross-section, then runs up to the control box. Grundfos limits the voltage drop to 3 % in the submersible cable, and large installations are sized at 1 % to reduce losses: use the cross-section table on the category page or ask us for the calculation.
The joint between motor cable and submersible cable must be perfectly watertight, as it is the leading cause of insulation faults in boreholes. The KM heat-shrink kits (J1, J7 from 1.5 to 6 mm², J2, J8 from 6 to 16 mm², J5 from 16 to 25 mm², kit F 4 × 10 to 50 mm², single-core kit No 6 from 35 to 120 mm²) join the conductors with crimped sleeves and then heat-shrink tubing; the MS plug-joint and termination kits are filled with resin for the MS 402 and MS 4000 cables. The fixing kit (16 stainless-steel buttons and 7.5 m of rubber band) holds the cable and the straining wire to the riser pipe, one clip every 3 m, for about 45 m of riser pipe.
Measure the insulation resistance of the cable and the joint before lowering the pump: below 0.5 MΩ, the joint must be remade. For high-power motors, single-core cables 1 × 25 to 1 × 185 mm² and M0 to M4 kits are available on request.
Applications: cabling a new SP pump, replacing a motor cable damaged while pulling the pump, extending a submersible cable when a borehole is deepened, remaking a faulty joint, spare kits for maintenance teams.
Official Grundfos distributor, SINES Export supplies Grundfos motors, protection units, cables and borehole accessories to installers, drillers, operators and NGOs, for worldwide export. For a replacement, send us the pump and motor nameplates: we check compatibility and prepare the complete motor, cable, joint and protection set. See also the SP submersible pumps, the RSI solar inverter and the “equipping an SP borehole” guide.
Motor cables by motor
| Motor |
Cross-section |
Lengths in the catalogue |
Connection |
| MS 402 | 4G1.5 mm² | 1.7 to 30 m | motor plug, 1 or 2 plugs |
| MS 4000 | 4G1.5 mm² | 1.7 to 20 m | motor plug, 1 or 2 plugs |
| MS 4000 RE (aggressive water) | 4G2.5 mm² | 2 to 60 m | motor plug |
| MS 6000 | 4G6 or 4G10 mm² | 5 to 30 m, 5 m leads | motor plug |
| MS 6000 R | 4G6 mm² | 20 m | motor plug |
Cable joint kits
| Kit |
Conductor cross-section |
Type |
| KM J1 (116251) | 1.5 to 6 mm², 3 or 4 conductors | heat-shrink, crimp connectors |
| KM J7 (116257) | 1.5 to 6 mm², 4 conductors | heat-shrink |
| KM J2 (116252) / J8 (116258) | 6 to 16 mm², 4 conductors | heat-shrink |
| KM J5 (116255) | 16 to 25 mm² | heat-shrink |
| KM F (96637330) | 10 to 50 mm², 4 conductors | heat-shrink |
| KM No 6 (116256) | 35 to 120 mm², 1 conductor | heat-shrink, one kit per conductor |
| MS joint (799901) | up to 2.5 mm² | joint with plug, resin |
| Termination (799902) | 4 to 6 mm² | cable termination, resin |
Common specifications
| Specification |
Value |
| TML-B cable | EPR sheath, ACS and KTW certified for drinking water; water up to 70 °C |
| Max. voltage drop | 3 % in the submersible cable (1 % advised on large installations) |
| Fastening | 1 clip every 3 m, kit for about 45 m of riser pipe |
Data from the Grundfos SP A, SP data booklet (50 Hz). Full data, versions and other voltages on the Grundfos Product Center or on request.