SP pumps: with a submersible motor supplied at 380 V and above, the CUE manual requires a sine-wave filter, whatever the power, for a motor cable of up to 300 m. The CUE and the filter are installed near the borehole, or further away with a screened cable running to a terminal box placed near the borehole.
SPE pumps: their MS6000P permanent-magnet motor requires a frequency converter. Grundfos offers the CUE for this purpose and recommends the RSI inverter for solar applications. The sine-wave filter is mandatory and is selected on the motor current at 100 Hz; the CUE is sized on the current, never on the power alone.
Grundfos settings for SPE pumps: ramp-up and ramp-down times of 3 seconds maximum, continuous operation at 55 Hz minimum to lubricate the bearings, voltage peaks limited to 800 V and never exceeding 850 V at the motor terminals, and dU/dt limited to 1 000 V/µs, hence the filter at the CUE output.
Motor protection: with a CUE, no additional overload protection is needed. Tempcon sensors do not work with a frequency converter; the motor temperature is monitored by a Pt100 or Pt1000 sensor connected to the MCB 114 module. The drop cable remains unscreened; screened cables are used on sites sensitive to electromagnetic interference.
Useful functions in boreholes: constant pressure, constant level, constant flow rate, dry-running protection, direction-of-rotation check, standby and low-flow stop (SPE data booklet).
Applications: drinking-water supply boreholes, irrigation, pumping stations on mains or generator power, upgrading a fixed-speed SP pump to variable speed.
Official Grundfos distributor, SINES Export supplies CUE frequency converters, their filters and their accessories to installers, integrators, engineering firms and operators, for worldwide export. Send us the motor nameplate and the cable length: we select the right CUE size and filter. See also the SP submersible pumps, the variable-speed SPE pumps and the CR and CRN pumps.
Grundfos selection: SPE motor, CUE and sine-wave filter
| MS6000P motor P2 (kW) |
Motor current (A) |
CUE 3 × 380-440 V |
P2 CUE (kW) |
I CUE (A) |
Sine-wave filter |
Filter current at 100 Hz (A) |
| 4.0 | 9.6 | 99616713 | 4.0 | 10 | 96754976 | 13 |
| 5.5 | 12.6 | 99616714 | 5.5 | 13 | 96754976 | 13 |
| 7.5 | 16.6 | 99616716 | 11 | 24 | 96754977 | 18 |
| 9.2 | 21.4 | 99616716 | 11 | 24 | 96754978 | 26.5 |
| 11 | 25.0 | 99616717 | 15 | 32 | 96754978 | 26.5 |
| 13 | 29.2 | 99616717 | 15 | 32 | 96755019 | 36 |
| 15 | 33.4 | 99616718 | 18.5 | 37.5 | 96755019 | 36 |
| 18.5 | 40.6 | 99616719 | 22 | 44 | 96755021 | 46.5 |
| 22 | 46.2 | 99616720 | 30 | 61 | 96755032 | 56 |
| 26 | 54.0 | 99616720 | 30 | 61 | 96755032 | 56 |
| 30 | 61.8 | 99616721 | 37 | 73 | 97774436 | 86 |
| 37 | 85.6 | 99616722 | 45 | 90 | 97775142 | 135 |
| 45 | 103.0 | 99616723 | 55 | 106 | 97775142 | 135 |
From the “Proposed by Grundfos, easy selection” table in the SPE data booklet: MS6000P motors 3 × 350 V at 3 000 rpm (100 Hz); 200-500 V filters selected on their current at 100 Hz. The motor cable is chosen according to the power: we specify it on the quotation.
When is an output filter required?
| Use case (CUE manual) |
CUE power |
dU/dt filter |
Sine-wave filter |
| SP, BM, BMB pumps with motors of 380 V and above | all | – | 0 to 300 m |
| MG71 and MG80 motors up to and including 1.5 kW | CUE above 1.5 kW | – | 0 to 300 m |
| Reduction of dU/dt and noise, low reduction | all | 0 to 150 m | – |
| Reduction of dU/dt, voltage peaks and noise, high reduction | all | – | 0 to 300 m |
| Motors of 500 V and above | all | – | 0 to 300 m |
Common CUE specifications
| Specification |
Value |
| Function | external frequency converter designed for Grundfos pumps, with a start-up guide for each pump family (CR, CRI, CRN, CRT, SP, SP-G, SP-NE…) |
| Control modes | open loop, constant pressure, constant or proportional differential pressure, constant flow rate, constant temperature, constant level, other constant value |
| Inputs and outputs | 1 RS-485 GENIbus port, 1 analogue input 0-10 V / 0-4-20 mA for the external setpoint, 1 analogue input 0-4-20 mA for the sensor, 1 analogue output 0-20 mA, 4 digital inputs (start / stop and 3 programmable), 2 programmable relays |
| Communication | GENIbus as standard; other protocols via a CIU communication unit |
| Motor cable | screened to comply with EN 61800-3; 150 m maximum screened, 300 m unscreened; beyond that, please consult us |
| Installation | IP20 / IP21 in a cabinet only; IP54 / IP55 never outdoors without protection against water and sun |
| Altitude | above 2 000 m, the CUE derates its output: a larger size may be required |
Sources: Grundfos CUE manual, Grundfos SPE data booklet and Grundfos 2026 catalogue.
Official Grundfos documents.
The online manual covers CUE units from 0.55 to 90 kW; for sizes of 110 kW and above, we supply the corresponding Grundfos manual with the quotation.
To select the size and the filter, contact us with the motor nameplate, the site voltage and the motor cable length.