The CUE 3 × 380-500 V in IP20 (0.55 to 90 kW) and IP21 (110 to 560 kW) is the version to be built into an electrical cabinet. It is available in a standard version and in an STO version, with a Safe Torque Off safety stop controlled by a single wire (Grundfos brochure).
The size is selected on the motor current and not on its power alone, as Grundfos points out for SPE pumps: in its selection table, a 7.5 kW SPE motor (16.6 A) requires a 11 kW CUE. The table gives the rated current of each size and the filters matched to it by Grundfos.
A sine-wave filter is mandatory with SP submersible pumps with motors of 380 V and above and with SPE motors. In other cases, a dU/dt or sine-wave filter reduces noise and voltage peaks at the motor terminals. The table columns give the filters matched by Grundfos to each size.
Applications: SP and SPE submersible pumps in boreholes, CR and CRN pumps in pressure boosting or process duty, pumping stations, irrigation, control cabinets.
Official Grundfos distributor, SINES Export supplies CUE frequency converters, their filters and their accessories to installers, integrators, engineering firms and operators, for worldwide export. Send us the motor nameplate and the cable length: we select the right CUE size and filter. See also the SP submersible pumps, the variable-speed SPE pumps and the CR and CRN pumps.
Sizes in the Grundfos 2026 catalogue
| Power P2 |
Rated current In (A) |
Matching dU/dt filter |
Matching sine-wave filter |
Versions |
| 0.55 kW | 1.8 / 1.6 | – | 96754941 | IP20 · IP20 STO |
| 0.75 kW | 2.4 / 2.1 | – | 96754941 | IP20 · IP20 STO |
| 1.1 kW | 3 / 2.7 | – | 96754972 | IP20 · IP20 STO |
| 1.5 kW | 4.1 / 3.4 | – | 96754972 | IP20 · IP20 STO |
| 2.2 kW | 5.6 / 4.8 | – | 96754973 | IP20 · IP20 STO |
| 3 kW | 7.2 / 6.3 | – | 96754973 | IP20 · IP20 STO |
| 4 kW | 10 / 8.2 | – | 96754974 | IP20 · IP20 STO |
| 5.5 kW | 13 / 11 | – | 96754976 | IP20 · IP20 STO |
| 7.5 kW | 16 / 14.5 | – | 96754976 | IP20 · IP20 STO |
| 11 kW | 24 / 21 | 97669799 | 96754977 | IP20 · IP20 STO |
| 15 kW | 32 / 27 | 97669799 | 96754978 | IP20 · IP20 STO |
| 18.5 kW | 37.5 / 34 | 97669799 | 96754978 | IP20 · IP20 STO |
| 22 kW | 44 / 40 | 97669799 | 96755019 | IP20 · IP20 STO |
| 30 kW | 61 / 52 | 97669869 | 96755021 | IP20 · IP20 STO |
| 37 kW | 73 / 65 | 97669869 | 96755032 | IP20 · IP20 STO |
| 45 kW | 90 / 80 | 97669869 | 97774436 | IP20 · IP20 STO |
| 55 kW | 106 / 105 | 97669896 | 97774436 | IP20 · IP20 STO |
| 75 kW | 147 / 130 | 97669902 | 97775142 | IP20 · IP20 STO |
| 90 kW | 177 / 160 | 97669902 | 97775142 | IP20 · IP20 STO |
| 110 kW | 212 / 190 | 97669905 | 97775146 | IP21 · IP21 STO |
| 132 kW | 260 / 240 | 97669905 | 97775146 | IP21 · IP21 STO |
| 160 kW | 315 / 302 | 97669905 | 97775148 | IP21 · IP21 STO |
| 200 kW | 395 / 361 | 97669906 | 97775148 | IP21 · IP21 STO |
| 250 kW | 480 / 443 | 97669906 | 97775149 | IP21 · IP21 STO |
| 355 kW | 658 / 590 | 93303172 | 93303174 | IP21 DC · IP21 STO DC |
| 400 kW | 745 / 678 | 93303173 | 93303175 | IP21 DC · IP21 STO DC |
| 450 kW | 800 / 730 | 93303173 | 2 × 97775149 | IP21 DC · IP21 STO DC |
| 500 kW | 880 / 780 | 93303173 | 2 × 97775149 | IP21 DC · IP21 STO DC |
| 560 kW | 990 / 890 | 93303173 | 2 × 93303174 | IP21 DC · IP21 STO DC |
Rated current: two values depending on the supply voltage range, the first at 3 × 380-440 V. Filters matched by Grundfos to each size; the choice between dU/dt and sine-wave depends on the pump and the cable length.
When is an output filter required?
| Use case (CUE manual) |
CUE power |
dU/dt filter |
Sine-wave filter |
| SP, BM, BMB pumps with motors of 380 V and above | all | – | 0 to 300 m |
| MG71 and MG80 motors up to and including 1.5 kW | CUE above 1.5 kW | – | 0 to 300 m |
| Reduction of dU/dt and noise, low reduction | all | 0 to 150 m | – |
| Reduction of dU/dt, voltage peaks and noise, high reduction | all | – | 0 to 300 m |
| Motors of 500 V and above | all | – | 0 to 300 m |
Common specifications
| Specification |
Value |
| Function | external frequency converter designed for Grundfos pumps, with a start-up guide for each pump family (CR, CRI, CRN, CRT, SP, SP-G, SP-NE…) |
| Control modes | open loop, constant pressure, constant or proportional differential pressure, constant flow rate, constant temperature, constant level, other constant value |
| Inputs and outputs | 1 RS-485 GENIbus port, 1 analogue input 0-10 V / 0-4-20 mA for the external setpoint, 1 analogue input 0-4-20 mA for the sensor, 1 analogue output 0-20 mA, 4 digital inputs (start / stop and 3 programmable), 2 programmable relays |
| Communication | GENIbus as standard; other protocols via a CIU communication unit |
| Motor cable | screened to comply with EN 61800-3; 150 m maximum screened, 300 m unscreened; beyond that, please consult us |
| Installation | IP20 / IP21 in a cabinet only; IP54 / IP55 never outdoors without protection against water and sun |
| Altitude | above 2 000 m, the CUE derates its output: a larger size may be required |
Sources: Grundfos CUE manual, Grundfos SPE data booklet and Grundfos 2026 catalogue.
Official Grundfos documents.
The online manual covers CUE units from 0.55 to 90 kW; for sizes of 110 kW and above, we supply the corresponding Grundfos manual with the quotation.
To select the size and the filter, contact us with the motor nameplate, the site voltage and the motor cable length.